Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Do the new AF and AFGF breakers have the time saver diagnostic (TSD) feature?
Issue:
Is the time saver diagnostic feature still available on the AF and AFGF breakers?

Product Line:
QO and HOM arc fault and dual function breakers

Resolution:
Yes, the time saver diagnostic feature is still built in to all AF and AFGF breakers. See the procedure below:
NOTE: Read all cautions and warnings in the literature and on the product.  Electrical work and troubleshooting should be done by an authorized person.

Fault Indication Procedure - Time Saver Diagnostics
  1. Place circuit breaker in the O/OFF position.
  2. Firmly press and continue holding the ‘TEST’ button through Step 4.
  3. Move handle to I/ON position.
  4. Circuit breaker should trip at one of the following times.
Trips Instantly (less than 1 second) Fault to ground; includes:
  • Arcing to ground
  • Shared neutral
  • Grounded neutral
  • Ground fault
Trips at 2.0 seconds Arc fault; includes:
  • Parallel arc fault
  • Series arc fault
Trips at 5.0 seconds Procedure complete; includes:
  • No Fault
  • Thermal overload
  • Short circuit
NOTE: Once you have recorded the TSD results. Please reset fault indication by using below procedure before leaving job site:
  1. Perform the fault indication procedure a total of 6 times
  2. Verify by performing fault indication procedure with a trip at 5.0 seconds (procedure complete) result.
An automatic reset of fault indication will occur if the circuit breaker has been powered continuously for 27 days.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings