What are IDLF faults on a ATV680 drive?
Issue:
IDLF faults on a ATV680 enclosed product
Product Line:
ATV680
Resolution:
When the device is in IDLE mode and you send a run command, but the device does not start to charge the bus within the adjusted energy saving timeout [idLt] (Factory settings: 5s // 8s for ATVx80 and ATVxB0), then the device will trip with IDLF.
Probable cause: The mains voltage is missing and the device cannot charge the DC Bus.
Remedies :Check mains voltage and ensure its availability. Check the DC bus voltage
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)“
Released for: Schneider Electric USA


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.