How can we help you today?

How to fix the Modbus reading error exception - type 2 on all the Modbus registers on PM8000 series meter?

Answer
Issue
While trying the read any of Modbus registers using Modbus Tester Tool on the PM8000 v3.0.0. template # 8000_v2.2.0.0.0 it reads the error “Exception response received – type 2”.

Product Line
PM8000 meter

Environment
Communications - Installation/Setup

Cause
The meter Modbus communication parameters were not configured correctly.

Resolution
The basic parameter for Modbus Map on the meter were configured correctly but not the advanced ones. This was required to use ION Setup Software in advanced mode and verify the “Security Options Modules” and look for their settings. Unfortunately, the module “S0P1 Modbus Map Access” was set to “NO” instead of “YES”, therefore editing the status of this module resolved the issue.
To do so, go to:
ION Setup
-> Hold down the “CTRL” key then click on the meter to access the ION Setup advanced Mode -> let roll down -> Click on “Security Options Modules”->  double click “Security Options 1” -> Setup Registers -> S0P1 Modbus Map Access - > Edit -> at the drop select “YES” then OK.
It will look like at the following figure.
img1

Reference documents:


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings