Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What does the diagnosis LED ON mean on TeSys Giga contactors ? How many on/off operations left after the LED is ON ?
The diagnostic LED shall be ON,
  1. when the contactor (switching module) reaches its end of life, means it have reached 85% of its electrical life. The electrical life depends on the operational voltage and current, utilisation category, make break current (AC3/AC3e) and depends on application type. So, the remaining number of operations shall also vary depending on multiple factors : 1 beat
  2. Coil undervoltage (A1-A2 <0.8Uc): 2 beats
  3. Coil overvoltage (A1-A2 )1.1Uc): 3 beats
  4. Internal fault: continuous beats
  5. Remote wear diagnosis (RWD) module (only when Advanced version) cannot enable remote alarm for central monitoring: 4 beats
Note that detail information refers to installation guide DOCA0189EN and here is the link: TeSys Giga Series - Contactors and Electronic Overload Relays - Installation Guide User guide | Schneider Electric

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings