Issue:
Customer has a ATV630U55N4 and Modbus TCP/IP and cannot change his I/O scanner table, in Somove. He was trying to add Register 3204 to his scanner table and it was grayed out and could not add it. He was positive the drive was not running. Tried power cycling the drive a couple of times and still could not add Register 3204.
Product Line:
ATV630
Resolution:
The I/O table is always grayed out, but it is possible to add registers. Check with the customer to see how he is trying to add the registers ?
If he is trying to double click, that will not work. He needs to right click on the mouse and then click on add. See attachment.
“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: