May NQ Panelboards with 175 A or 200 A branch circuit breakers be certified for seismic applications?
Issue:
Which are the NQ Panelboards branch breakers certified for seismic applications?

Product Line:
NQ Panelboard

Environment:
Application

Resolution:
No, seismic certification of NQ panelboards requires that all branch circuit breakers be bolt-on, and not plug-on.  This requires the selection of QOB, QOB-H, QOB-VH, or QHB branch circuit breakers.