How can I change the language on an ATV320 drive?

Resolution :

The drive's default language is English. However, during programming or commissioning, the language setting may sometimes be changed. Follow the steps below to restore the drive language to English:

  1. Press the ESC button repeatedly until rDY is displayed on the screen. Then press ENT to access the menu.
  2. Scroll down to the third menu item, InF (Interface).
  3. Press ENT, scroll down two items, and then press ENT again. This should display LnG (Language).
  4. Press the green button (ENT) to open the list of available languages.
  5. English is located at the top of the list.
  6. Select English and press the green button (ENT) to save the setting.

The drive interface should now be displayed in English.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings