How can we help you today?

How to fix the "ExitCode ERROR!" issue when starting Vijeo Designer Runtime?

If the OS on the IPC is Win10 64-bit, user will see "ExitCode ERROR!" when starting Vijeo Designer 6.2 SP11 Runtime.

To solve the issue, user can upgrade to Vijeo Designer 6.2 SP11 HF5(6.2.11.2301_6.2.11.2301).

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings