How can we help you today?

How to update Exlhoist software version to 4.0.20?

Issue:
Unable to update XLhoist Configuration Software version from 4.0.18

Product line:
Industrial Wireless Remote Control

Environment:
Harmony eXLhoist Industrial Remote Controllers

Resolution:
To avoid any problem, it’s mandatory to uninstall correctly the old version 4.0.18 before install the new one. See attached document

Schneider Electric USA

Attachment(s)
Exlhoist Configuration software_New_Version.pdf [172.82 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings