Why is there no output voltage, when the ATV71 drive is running?

Issue:

No output voltage from the ATV71 drive

Product Line:

ATV71/ATV621

Resolution:

Power down and perform static checks on the outputs to the +/- bus ( PA/+ to PC/-).

Power up the drive and recheck all the motor parameters, including the Motor control Type parameter.

Then could go to 1.10 menu and run the transistor tests.

If all these test pass, then make sure the Motor Control Type is set to V/F 2 pts ( 1.4 menu)

and then go to 1.8 menu: set OPL to no. Run the drive at 20, 40 and 60 hz and measure

all the outputs to see if they are all balanced. If they are balanced, then appears the drive

is ok. Would suggest to disconnect the motor and megger it out with 1000v megger.

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings