Issue:
Can trip units for H, J, and L frame circuit breakers be replaced?
Product Line:
Circuit Breakers
Environment:
Powerpact H, J, L frames
Resolution:
Trip units for Powerpact H, J, and L can be replaced unless they have been sealed at the factory.
Can trip units for H, J, and L frame circuit breakers be replaced?
Product Line:
Circuit Breakers
Environment:
Powerpact H, J, L frames
Resolution:
Trip units for Powerpact H, J, and L can be replaced unless they have been sealed at the factory.
- All I-Line breakers in this range have sealed trip units and are NOT replaceable. I-Line breakers all have the letter "A" in the third position in the catalog number
- for example, HJA36100U31X.
- Unit mounted circuit breakers may be purchased with sealed or replaceable trip units
- Breakers with replaceable trip units have a "T" in the catalog number immediately following the Ampere rating,
- for example, HJA36100TU31X or HGA36100T
- Breakers with sealed trip units will have no T in the catalog number in this position,
- for example, HJA36100U31X or HGA36100
- Breakers with replaceable trip units have a "T" in the catalog number immediately following the Ampere rating,
Released for:Schneider Electric USA