How many bus bars can be ran with the GV2G05 inside the enclosure?

Issue:

Quantity of busbars that can be used inside the enclosure for interconnect GV2's

Product Line:

TeSys Deca Contactors

Environment:

Panel building

Resolution:

There is no really limit of busbars that can be used for the GV2. The maximum use of busbars Its based Between supply, heat generation, panel space, etc

The biggest limitation is actually around the max ampacity of contactor. The qty really depends on the application

so for example on 63 Ampacity if customer has a bunch of 10A devices. The max number of GV on bus would be 6 (6x10=60A)

any configuration for bus would work but that ampacity is the stopping point.

however, in the same situation, if there are a bunch of 2 AMP motors, theoretically you can have up to 31 with continuous

bus connections if the supply and the panel can handle that with heat dissipation and size.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings