The BMXDDI3202 wiring diagram is incorrect in the 'Discrete Input/Output Modules User Manual' dated 11/2020
The BMXDDI3202 wiring diagram is incorrect in the Modicon X80 Discrete Input/Output Modules User Manual, 11/2020, part number 35012474.18, page 193.

Incorrect wiring diagram

The DC power supply wiring is incorrectly shown (positive and common is wired backwards).
BMXDDI3202 incorrect wiring

Correct wiring diagram
The BMXDDI3202 wiring diagram is correct in the earlier version of the Modicon X80 Discrete Input/Output Modules User Manual, 10/2019, part number 35012474.16, page 203.

BMXDDI3202 correct wiring

This will be corrected in the next User Manual version.