How can we help you today?

The BMXDDI3202 wiring diagram is incorrect in the 'Discrete Input/Output Modules User Manual' dated 11/2020

The BMXDDI3202 wiring diagram is incorrect in the Modicon X80 Discrete Input/Output Modules User Manual, 11/2020, part number 35012474.18, page 193.

Incorrect wiring diagram
The DC power supply wiring is incorrectly shown (positive and common is wired backwards).
BMXDDI3202 incorrect wiring

Correct wiring diagram
The BMXDDI3202 wiring diagram is correct in the earlier version of the Modicon X80 Discrete Input/Output Modules User Manual, 10/2019, part number 35012474.16, page 203.
BMXDDI3202 correct wiring

This will be corrected in the next User Manual version.


Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings