Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can I use a 3-phase transfer switch on a 1-phase system?
Answer: YES.  3-phase transfer switches come with a microprocessor controller that can be set / programmed for 1-phase sensing.

Change the dipswitch settings from 3-phase to 1-phase and connect power cables on phases A and C.

Phase Configuration Dipswitches
Location of Dipswitches

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings