What is an INFL error on the ATV340 drive?

Issue:

What is an INFL error on the ATV340 drive?

Product Line:

Altivar 340

Environment:

All

Cause:

Internal time clock error. Communication error between keypad and drive or a clock oscillator start failure.

Resolution:

Reinitialize the communication by following steps.

  1. Power off the drive and wait until display is blank and repower on to confirm issue.
  2. Disconnect keypad from the drive and remove batter if applicable.
  3. If problem persists, try a different keypad if possible.