Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
PME2021 Installation Error with Driver Package TH110 / CL110
Issue:

During PME2021 Installation, the step "InstallUDFDrivers" is failing.

PME CL110

Root cause:

This is a known issue with non-English Operating Systems.

The following error can be seen on the Installation Log:
Install_log

Resolution:

If this is the only step that who failed, you can click on "close" button of the PME Installer.

Download and install the PME2021 Cumulative Update 1 (or more recent Cumulative Update).

The issue has been corrected in the PME 2021 CU1.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings