Is the BMXNOE0100 hot swappable?

Issue

If there is a need to replace an NOE module with the same model number but not making any configuration changes, can it simply be hot swapped?

Product Line

Modicon M340

Resolution

If simply replacing the hardware and keeping all addressing/configuration parameters the same it can be hot swapped. This means that the PLC can remain running uninterrupted. Once the new NOE is in place and the cable is attached it will assume the configuration information provided by the M340. You will now have an Ip address on your network that has switched MAC addresses. This may or may not raise a flag on your network depending specifically on your installation. This Applies to the BMXNOE0110 as well.

Schneider Electric USA

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings