Can the ATV320 drives be used at high elevation?

The ATV320 series drives can be used in higher elevation applications with the following limitations:

When connected to TT/TN or IT power systems, The ATV320 products is limited at 1000m without derating in M2, M3, N4 and S6 voltage ranges.

Corner grounded systems in N4 and S6 are not compliant with IEC specifications.

Corner grounded system in M2 and M3 versions (not allowed for N4 and S6) are limited to 2000m with derating of the current by 1% per 100 meters over 1000m.

The M3 and N4 versions can go up to 3000 meters on TT/TN and IT systems with derating of the current by 1% per 100 meters over 1000m.
M2 and S6 drives are not approved for this elevation and no drives are allowed on a corner grounded power system.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings