How can we help you today?

Is it normal to have continuity between the phases when the transformer is not yet energized?

Issue:

Low voltage transformer having continuity between phases when not energized

Product Line:

LV Transformers

Environment:

All Low voltage transformers, EE, EX, EXN

Resolution:

Continuity is normal between the phases of the primary and secondary sides of the transformer even if they're not energized (H1 and H2 or H2 and H4 etc) or (X1 and X2 or X2 and X3 etc). What's not normal is having continuity on the primary and secondary sides (H1 and X1 or H2 and X2 etc).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings