Can you use the NQMB2Q on a 100A NQ panel?

Issue:
Needs an 18 circuit NQ panel with a 100A QD main breaker


Product Line:
Panelboards


Environment:
NQ Panelboard

Cause:
Field conversion

Resolution:

NQMB2Q main breaker kit will not work on an NQ 100A like the NQ18L1C

The 100A interior has main lugs rated for #6-2/0 AWG while the main breaker kit has cables rated for 4/0 AWG.

There is no way to make the connection between the breaker and the interior.

Schneider Electric USA