Ecostruxure Machine Scada Expert - Display trend Date and Time at the cursor position.

Issue:
How can we display the Date and Time at the cursor position on the Trend object?

Product Line:
EcoStruxure Machine SCADA Expert (all versions)

Resolution:
The date and time at the cursor position is not directly available on the trend graphic. In order to display it, some elements must be configured.

1- Create a global "String" tag that will receive the date and time:

Project Explorer - Global tab - right click on "Tag List" to insert a tag.

Insert Tag

In the window, enter the name of the tag and select "String" as the type.

Create the String Tag

2- Double click on the "Trend Control Object" to open the properties window.

Click on the "Axes" button.

Then the "Cursor" button in the new window.

Enter the tag name in the "Value Output" field.

Associate the string tag to the axes cursor value output

3- On the graphic page, add a text object to display the date and time.

Go into the "Draw" menu, select the "Text" tool and add a text field.

Define the properties of text field, then click the "Text data link" button.

Define the Text Data link to display the string tag

In the "Tag/Expression", enter the tag name.

Save the modifications.

Test, the date and time at the cursor position should display.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)
Test_Trend.zip [304.62 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings