How can we help you today?

SDSA1175 SDSA1175T Selection, Voltage, Wiring, and Ground

Ordering the wrong SPD requires return/exchange, if possible. One SPD cannot substitute for the other. It is crucial to order the correct SPD with the appropriate voltage code.

  • It is essential to order the appropriate SPD with the correct voltage code.  If you have 120V 1P, the SDSA1175T is the correct SPD, not the SDSA1175 120/240V.
  • It is essential to order the appropriate SPD with the correct voltage code.  If you have 240/120V 1P, the SDSA1175 is the correct SPD, not the SDSA1175T 120V.

SDSA1175 and SDSA1175T units lack a green wire for connection to the electrical system ground. The neutral wire, usually a larger #AWG wire, provides a lower impedance path back to the N-G Bond. SDSA1175 and SDSA1175T have a white neutral wire, used for surge current dissipation back to the electrical system service entrance.

Details:

  • SDSA1175: Three-wire surge suppressor for 120/240 VAC services (2 phase conductors, a neutral, and no ground).
  • SDSA1175T: Two-wire surge suppressor for 120 VAC services (1 phase conductor, a neutral, and no ground).


Product Family   -   SDSA1175 SDSA1175T

The SDSA1175 is designed for 120/240V single phase (L1-L2 & N) 36kA

The SDSA1175T is designed for 120V single phase (L1 & N) 36KA
SDSA 11775 and SDSA1175T Data

Schneider Electric USA

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings