Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
BCM Summary button does not open branch circuit view on the HDPM6000 HMI
Issue
Selecting the "BCM Summary" button on the HDPM6000 HMI does not open the circuit view to view the individual branches.  The button appears to not be working.

Product line
HDPM6000
HDPM6000 HMI

Resolution
1. Open the HDPM6000 web page and login
2. Navigate to the "General Settings" tab
3. Set the "Phase summary" setting to "Circuits" or "Split Circuits"
4. Select the "Save circuit settings"

If "3 phase meter" is selected on the web page settings, the HMI will not show the branches when the "BCM Summary" button is pressed.

Webpage settings

Schneider Electric USA

Explore more
Range:
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings