What is the QMB branch switch replacement criteria?

Issue:
QMB branch switch information

Product Line:
QMB fused switches

Environment:
QMB Branch switches



Cause:
Selection criteria

Resolution:

Type QW (38-inch Wide) Manufactured Before 1984

  • Type QW panelboards were built to accept bolt-on 400 A and 600 A Series 1-4 switches. 30-200 A Series D2 switches may be installed using the plug-on extension assembly.

Type QM (31-inch Wide) Manufactured Before 1961

  • Panelboards manufactured before 1961 have the interior mounting rails facing inward (toward the bus). Switches and circuit breakers that fit in this interior type are obsolete.

Type QM (31-inch Wide) Manufactured After 1961 But Before October 1984

  • Panelboards manufactured after 1961 have the interior mounting rails facing outward (away from the bus). This interior accepts Series 1-4 switches and Series D2 switches (shown above with required rail extensions). Order the Series D2 switch (includes mounting rail extensions).

Type QMB Manufactured After October 1984

  • Series E1 panelboards will accept only Series E1 or E2 switches.
(See attached Supplemental Digest.)

qmb

Schneider Electric USA

Attachment(s)
SD_0100CT1902_SEC-13.pdf [2.09 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings