Control Expert Instruction Formal Input Parameters
Issue
Looking for a setting to allow an instructions formal input parameters to be written to directly.
For example, the instruction TON has the name of it as TEST_TMR, the parameter TEST_TMR.PT can not be written directly to in the program without using an actual parameter connected to the input pin PT.
The same goes for counters, if there is a CTU and the name is TEST_CTU, the parameter TEST_CTU.PV can not be written to in the program to set the Preset Value.
When attempted, Control Expert produces the error message.
{MAIN : [MAST]} : (l: 41, c: 31) E1172 TEST_TMR.PT cannot be accessed
{MAIN : [MAST]} : (l: 41, c: 31) E1053 input variable 'TEST_TMR.PT' must not be assigned
Product line
Control Expert, Unity Pro
Resolution
Unlike the formal output parameters such as TEST_TMR.ET, the formal input parameters can only be written to internally from the Function Block as a matter of IEC design requirements.
There is no setting to use that would allow it.
Released for: Schneider Electric USA