Issue:
The RPI setting does not appear to impact the Communication timeout as described in the option card manual.
Product Line:
Altivar 600 series drives: ATV630, ATV650, ATV660, ATV680 when using Ethernet option cards VW3A3720 or VW3A3721
Cause:
Documentation needs updated
Resolution:
The communication timeout related to the Ethernet option card is an internal parameter TOUT (register 64211, units are 0.1 seconds).
This parameter can be accessed using SoMove by adjusting the Holdup Time under the Modbus TCP settings in the option card tab. The time set applies to both Modbus TCP and Ethernet IP communications.
Attach Video here:
The RPI setting does not appear to impact the Communication timeout as described in the option card manual.
Product Line:
Altivar 600 series drives: ATV630, ATV650, ATV660, ATV680 when using Ethernet option cards VW3A3720 or VW3A3721
Cause:
Documentation needs updated
Resolution:
The communication timeout related to the Ethernet option card is an internal parameter TOUT (register 64211, units are 0.1 seconds).
This parameter can be accessed using SoMove by adjusting the Holdup Time under the Modbus TCP settings in the option card tab. The time set applies to both Modbus TCP and Ethernet IP communications.
Attach Video here: