Issue:
The currents are low and balanced but overload trips on S-Flex. Overload setting is good.
Product Line:
ATV212, S-Flex
Environment:
All
Cause:
NA
Resolution:
If using multiple motors on ATV212 or S-Flex drive, then try setting parameter Pt=0(Constant V/Hz).
Constant V/Hz is designed for running multiple motors at the same time(motors in parallel).
The currents are low and balanced but overload trips on S-Flex. Overload setting is good.
Product Line:
ATV212, S-Flex
Environment:
All
Cause:
NA
Resolution:
If using multiple motors on ATV212 or S-Flex drive, then try setting parameter Pt=0(Constant V/Hz).
Constant V/Hz is designed for running multiple motors at the same time(motors in parallel).
Released for: Schneider Electric USA



