How can we help you today?

Forcing X80 IO Analog inputs with the modules Device DDT.

Issue

Does forcing an Analog Input in an M580 configuration also clear the broken wire error for the channel?

Product Line

Modicon M580, Control Expert, Unity Pro

Resolution

No. All that it does is set the ANA.FORCED_VALUE to the ANA.VALUE while ANA.FORCED_STATE is true after enabling ANA.FORCE_CMD.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings