Forcing X80 IO Analog inputs with the modules Device DDT.

Issue

Does forcing an Analog Input in an M580 configuration also clear the broken wire error for the channel?

Product Line

Modicon M580, Control Expert, Unity Pro

Resolution

No. All that it does is set the ANA.FORCED_VALUE to the ANA.VALUE while ANA.FORCED_STATE is true after enabling ANA.FORCE_CMD.

Schneider Electric USA

Forcing X80 IO Analog inputs with the modules Device DDT.

Issue

Does forcing an Analog Input in an M580 configuration also clear the broken wire error for the channel?

 

Product Line

Modicon M580, Control Expert, Unity Pro

 

Resolution

No. All that it does is set the ANA.FORCED_VALUE to the ANA.VALUE while ANA.FORCED_STATE is true after enabling ANA.FORCE_CMD.

Schneider Electric USA

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.