Forcing X80 IO Analog inputs with the modules Device DDT.

Issue

Does forcing an Analog Input in an M580 configuration also clear the broken wire error for the channel?

Product Line

Modicon M580, Control Expert, Unity Pro

Resolution

No. All that it does is set the ANA.FORCED_VALUE to the ANA.VALUE while ANA.FORCED_STATE is true after enabling ANA.FORCE_CMD.