Issue:
ATV212 drive getting Err 1 faults
Product Line:
ATV212
Environment:
Err 1 faults
Cause:
n/a
Resolution:
Err 1 faults on the ATV212 indicates that the scaling parameters for either VIA or VIB are not set correctly. Please check parameters F201- F204 (for VIA) or F210 to F213 (for VIB).
Released for: Schneider Electric USA



