BMXDRA0815 relay module 125 VDC switching

Issue

What is the max switching current of the relay for a typical inductive 60VDC and 125VDC application?

Product Line

Modicon X80

Resolution

@ 60VDC (for operation in temperatures less than 60 deg C)

40W(1)/60VDC = 660ma for 40k cycles maximum

@ 125VDC (for operation in temperatures less than 60 deg C)

15W(5)/125VDC = 120ma for 100k cycles maximum

Modicon X80 Discrete Input/Output Modules User Manual, 11/2020, part number 35012474.18

Page 229 shows the maximum number of relay cycles for (1) 60VDC and (5) 125VDC as reference above.

(1) 0.04 x 106 cycles = 40,000

(5) 0.1 x 106 cycles = 100,000