Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to configure EIP buscycle with BMED581020 (IEC 61499)
Context: Example BusCycle EIP configuration (IEC 61499) between BMED581020 and BMEP586040.
EIP configuration BMED581020

BMED581020 EIP configuration buscycle

BusCycleTime must be greater than RPI O -> T + RPI T -> O

Example:
BusCycleTime (80ms) >> RPI O -> T (30ms) + RPI T -> O (30ms)

Note: if there are several devices, take the highest RPI O -> T and RPI T -> O.


Product line:
EAE, EIP, Buscycle, Time, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings