How can we help you today?

How to change parameter of BMED581020 PLC (IEC 61499)

Where is PLC parameter: Open Logical Device

logical device M580D

Modification of parameter: Select OVERWRITE on “Deploy Setting” by example

PLC parameter M580D

By default, “Auto start after deploy” is False

PLC parameter M580D

After deploy your PLC will be in “Stop” mode.

Deploy false parameter M580D

Change “Auto start after deploy” parameter is True

change parameter true M580D

SAVE and BUILD

Now need to send this parameter in PLC.
Deploy Device Configuration + Deploy and restart

deploy device configuration M580D

Deploy and restart


Now when you deploy your application PLC is in “RUN” mode.

after deploy RUN

Product Line
EAE 22.0, BMED581020, IEC 61499, PLC parameter
Environment
Windows, EcoStruxure Automation Expert 22.0

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings