What class of fuse do ALL the 60 A, 240 Vac max, heavy duty safety switches accept?
Product Line:
Heavy Duty Safety Switches
Resolution:
HDSS = heavy duty safety switches
SCCR = short circuit current rating
ALL the 60 A, 240 Vac max, HDSS accept Class H or K fuses as standard. Options include Class R fuses (field install Class R Fuse Kit). With Class H or K fuses installed, the switches are UL/CSA listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R fuses (and Class R Fuse Kit installed), the switches are UL/CSA listed for use on systems with up to 200,000 RMS Symmetrical Amperes available fault current.
NOTES:
1) DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability, and will void the warranty.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.