You must used “MIBGET” function block.

Where is the list of “MIBGET” functionality?

For CPU load:

For Memory:

Example of application with CPU load:



Product line:
EAE, CPU load, Memory load, MIBGET, Simulator, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0
Where is the list of “MIBGET” functionality?
For CPU load:
For Memory:
Example of application with CPU load:
- Add “MIBGET” function block like this
- Change parameter VALUE1 “STRING” to “UDINT” of “MIBGET” function block
- Save + Compile + deploy + RUN your application
- Generate event on REQ => result of value is 118 => CPU load = 11.8%
Product line:
EAE, CPU load, Memory load, MIBGET, Simulator, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0
Released for: Schneider Electric USA









