Why "OFSLog" shows the message “Not enough space”?

 

Issue

Why does OFSLog display the message "Not enough space" and why does OFS stop responding after running for some time?

Product Line

  • OPC Factory Server (OFS)

Environment

  • OFS V3.63
  • OFS V3.63 SP2

Resolution

In some situations, the memory consumption of the OFS process may continuously increase over time. When the available memory becomes insufficient, OFSLog may display the message "Not enough space", and OFS may stop operating correctly.

This behavior is caused bymemory fragmentation, which can have effects similar to a memory leak. The issue is related to the GarbageCollector feature, which is enabled by default in affected versions.

print screen

To deactivate the GarbageCollector:

  1. Stop the OFS service.
  2. Open the following file:
    C:\ProgramData\Schneider Electric\OFS\3.63.0.0\ofsinternal.xml
    
  3. Locate the following entry:
    <add value="true" key="GarbageCollector"/>
  4. Change it to:
    <add value="false" key="GarbageCollector"/>
  5. Save the file and restart OFS.

After the change, verify in the OFS log that the GarbageCollector is not active.

Applicable Conditions

  • Applies to OFS V3.63.
  • In OFS V3.63 SP2, the GarbageCollector is disabled by default.
 

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings