- Verify that the Stop Button isn’t locked by rotating it 90° clockwise to unlock it.
- If not, unplug the connector from the Electric Vehicle, switch off the power supply to the charger, wait 10 sec minimum before energizing again the EVlink Home Smart, wait for the charger to become ready (LED is constant green or pulsing yellow) before reconnecting the connector to the Electric Vehicle.
- Failing that, check that the Neutral and Phasis are correctly connected.
- Failing that, check that the power supply is securely wired to the charger’s PE (Protective Earth) terminal.
- Check if the VE asked to activate the ventilation.
- If not, unplug the connector from the Electric Vehicle, switch off the power supply to the charger, wait 10 sec minimum before energizing again the EVlink Home Smart, wait for the charger to become ready (LED is constant green or pulsing yellow) before reconnecting the connector to the Electric Vehicle.
- Failing that, check that the Neutral and Phasis are correctly connected.
- Failing that, check that the power supply is securely wired to the charger’s PE (Protective Earth) terminal.
- Check if the VE asked to activate the ventilation.