On previous generations of SCADAPack such as the SCADAPack 32, SCADAPack 3xx or SCADAPack 4203 series RTU's, Realflo licenses were specific to type and run number. For example a SCADAPack 4203 could have 2 gas runs OR 1 gas, 1 water and 1 liquid. These were determined by the actual license of the device.
On a SCADAPack x70 RTU, Realflo licenses are for number of runs. Type is decided by the user. Example a user could have 10 flow runs licensed. This could be for any type of runs. The user can decide via the Realflo configuration if it uses 2 gas runs, or 9 liquid run and 1 water run, or 5 gas runs with 5 liquids runs or even just 1 gas run. Essentially any combination of 10 runs or less.
To check to see how many runs a SCADAPack x70 device is licensed for, the user can open either RemoteConnect or Realflo.
RemoteConnect
- Create a default 47x or 57x project using RemoteConnect version 2.6.1 or later
- Connect to the RTU via RemoteConnect and go online (via Modbus TCB/USB or DNP3 USB)
- Check the "Online Diags - SPx70 Controller tab"
- Refresh the page
- The amount of flow runs that can be configured in Realflo is displayed
Realflo
- Open Realflo version 7.00 or greater in Expert mode
- Select "File -> New" from the drop down menu
- On the Create New pop-up, select "Create 1-run gas configuration with default values"
- Select Configuration -> PC Communication Settings
- Set proper PC Communication settings as per your set-up
- Select Configuration -> Flow computer information from the drop down menu
- The amount of flow runs available and that are configured is available
For more information, please see the RemoteConnect and Realflo help files installed with each software respectively.
Released for: Schneider Electric USA