Can a PM5500 series meter have a Modbus TCP/IP and BACnet IP master connection simultaneously?

Issue
A customer needs to connect one PM5500 meter to two different sites using two different protocols.

Product Line
PM5560, PM5563

Environment

Communications

commissioning

Resolution

BACnet and Modbus are different communication protocols.

  • BACnet is a broadcasting protocol where devices continuously listen to the master. When their turn (token) comes, they respond to the master.
  • Modbus, on the other hand, is a request/reply protocol that provides services defined by function codes. These function codes are elements of the Modbus request/reply Protocol Data Unit (PDU).

The PM5500 meter can communicate with both systems simultaneously without any issues.

PM5000 series meter documentation: FA234023

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings