Masterpact NW is not communicating breaker status correctly

The cause for this is usually incorrect installation of the Communication Switch Assembly.
  • First ensure that the silver colored shaft coming down vertically from the SDE switches is free to move up and down.  If not, grasp the shaft with a needle-nose plier and move it up and down until it is free.
  • If this doesn't correct the issue, remove and re-install it per the linked instruction bulletin 48049-139-02.
If the switch assembly is broken or is still non-functional, replace it.  It is only available as a component of kit # S48384.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings