Why can't I download to a brand new HMIGTO / HMIGK with Vijeo Designer 6.2 SP11 or older?

Issue
Can't download to a new HMIGTO / HMIGK using Vijeo Designer v6.2 SP11 or older.

Product Line
HMIGTO and HMIGK families of HMIs

Environment
Vijeo Designer v6.2

Cause
The new HMIGTO/HMIGK families have a hardware component change that requires newer Vijeo Designer versions.

Resolution
The Harmony HMIGTO and HMIGK families of HMIs withSV4.0 or later on the sticker on the back of the HMI need to be programmed with Vijeo Designer v6.2 Service Pack 12 minimum.

Please find the download links for SP12 here:
https://www.se.com/us/en/faqs/FAQ000239885/

The Harmony HMIGTO and HMIGK families of HMIs withSV5.0 or later on the sticker on the back of the HMI need to be programmed with Vijeo Designer v6.3 minimum. Note: Vijeo Designer v6.3 requires a new license.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings