EcoStruxure Machine SCADA Expert v2020 SP3 - Modifying background color of Alarm object crashes the application.

Issue:

In EcoStruxure Machine SCADA Expert v2020 SP3, place an alarm object on the screen and click to change the background color. Select a color from the Standard Colors pallet and the software will crash and display the below message.

Crash Error Message

Interestingly enough, if you click the Edit Custom Colors, and chose a color from that pallet, it does not crash the software.

Customer work around

Product Line:

Specific to EcoStruxure Machine SCADA Expert Version 20, Service Pack 3.

Resolution:

This is a known issue on this specific version.

Please check the attached HotFix: EMSE 2020.3.00.01

Please check the ReadMe file for installation instruction.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)
EMSE 2020.3.00.01.zip [1.11 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings