How can you setup a custom display to show temperature or pressure as the PID setpoint on the ATV212 Drives?

Resolution:

You can configure the ATV212 drive's custom display to show process values such as temperature or pressure as the PID setpoint. The example below demonstrates how to display a temperature range of 32°F to 124°F.

Example Configuration

  1. Calculate the minimum display value:

    • Minimum temperature: 32°F
    • Formula: 32 ÷ 1.5 (F702) = 21.33
    • Set F706 = 21.33
  2. Configure the following parameters:

F701 = 1 (Default)
F702 = 1.5
F703 = 1
F705 = 1
F706 = 21.33
FNOD = 3 (PID keypad setpoint display)
F360 = 1 (VIA)
V380 = Yes (Enable PID inverse mode for temperature PID applications)
  1. Verify the maximum display value:
    • Temperature span: 122°F - 32°F = 90°F
    • Adjusted span: 90 - 21.33 = 68.67
    • Formula: (68.67 × 1.5) + 21.33 = 124°F

Result

After completing the configuration, the drive's display allows the PID setpoint to be adjusted using the Up and Down keys. The displayed setpoint range will be approximately 32°F to 124°F.

Note: The display shows only the numeric value. Units such as °F, PSI, or other engineering units are not displayed.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings