How can we help you today?

What is the handle force required to operate the handle of a PowerPacT H Frame circuit breaker?

Product Line: Molded Case Circuit Breaker

Resolution:
The following forces are required to operate the handle of PowerPacT H Frame circuit breaker:

ON - 14.8 lbs  (force required to close the breaker by pushing the handle from OFF to ON)
OFF - 16 lbs (force required to open the breaker by pushing the handle from ON to OFF)
RESET - 20.7 lbs (force required to reset the breaker after a trip by pushing the handle from TRIPPED to OFF)

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings