Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Power Tags M250/M630 active energy delivered incorrect value in PaS FW 1.5.1 web page
Issue
Power Tag sensors M250/M630 active energy delivered value issue in PaS FW 1.5.1 web page.

Product Line
Power Tag M250/M630
PaS 600/800
PME/EPO

Environment
Power Tag NSX M250/M630 FW 001.001.001 & FW 001.003.003
PaS 600/800 FW 001.005.001

Cause
Power Tag sensors M250/M630 active energy delivered values are out of scale by 1000 in PaS FW 1.5.1 web page.

Resolution
This issue is fixed in latest Firmware 001.006.000. Recommended to upgrade the FW of PaS to 001.006.000.


NOTE:
This issue is not seen in PaS earlier FW 001.004.000. This is present only in FW 001.005.001.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings