Can You Scale Signals Transmitted Through the ATV930 Multi Drive Link (MDL) in a Client/Server Configuration?

Resolution:

It is not possible to let say “customize” data passing through the digital link.

The Client sends the speed and the torque references to Servers plus some data needed to have the function working well but no customer access to these data.

As speed reference is sent by the Client, you can configure a function (Jog, reverse, …) only at client level.

The Server will follow the Client.

As reminder, be sure the Server is in RUN mode before the Client.

The Server will be in RUN waiting the “final RUN” delivered by the Client as soon as you give RUN order at Client level.

With MDL

Scaling of the speed is not possible (old request done in our side but still not available)

Scaling of the torque at Server level is possible through the Parameter TRT

TRT add on to FAQ

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings