What is the replacement bottom plate for an EX transformer with a 25J type enclosure?

Product Line:

Low Voltage EX/EXN Transformer

Environment:

LV Transformer

Cause:

Looking for bottom plate for EX225T3H transformer that is mounted high up, i.e. billboard.

Resolution:

The EX225T3H has a 25J type enclosure. The 25J enclosure is designed to be "Switchboard Style", meaning it mimics our Switchboard Product's open-style bottom access for ease of conduit entry and wire bending, etc. As a result, the open bottom enclosure does not have an option for a bottom plate available at this time. We do not offer any bottom plate for Type 25J enclosure. Since the Transformer is normally placed on a concrete floor or pad, the customer may fabricate a shelf or metal barrier below the Transformer to prevent access to the underside, but any such installation is subject to the discretion of local inspection authorities.