How can we help you today?

What is the current generated for a channel on the BMXAMO0410 for a 10VDC signal?

Issue
I am trying to determine voltage drop from a 2-10VDC signal generated by a BMXAMO0410 AO Module.
What is the current generated at the device to provide the 10VDC signal?

Product Line
X80 Analog I/O Modules - BMXAMO0410

Environment
Electrical characteristics

Resolution
For the BMXAMO0410, per channel, the minimum load impedance for voltage output is 1 kOhm.
Where the min load impedance is 1 kOhm, that means at +10VDC, the max current draw cannot exceed 10mA. 10vdc/1000 ohm= 10mA.

Also see: https://en.wikipedia.org/wiki/Output_impedance

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings