How can you reset your HMI baud rate if you change both HMI and fieldbus baud rates to 9600 on the ATV600 or ATV900 Drives?

Resolution:

If both the HMI (keypad) and fieldbus baud rates are set to 9600, the HMI may lose communication with the drive. To restore the connection, you need to reset the HMI baud rate back to 19.2 kbps using one of the following methods:

✅ Option 1: Connect using SoMove with a cable

  1. Order and use the TCSMCNAM3M002P communication cable
  2. Connect your PC to the drive
  3. Open SoMove software
  4. Access the drive settings and reset the HMI baud rate to 19.2 kbps

✅ Option 2: Connect via Ethernet

  1. If you know the Ethernet password, connect the drive to your network
  2. Use SoMove over Ethernet
  3. Locate the HMI communication settings
  4. Change the HMI baud rate back to 19.2 kbps

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings